Description
![]()
Measurement Range: 0 to 2 bar (0 to 20 mH2O).
Output Signal: 4-20mA
Power Supply: 12 to 30 Vdc.
Cable Length: Available in integrated wire lengths of 10 m, 20 m, and 30 m tailored to the measurement depth.
Accuracy & Stability: 0.5% F.S. precision combined with a maximum long-term stability of 0.2% F.S..
Working Temperature: -40°C to +85°C.
Protection Class: IP68.
Materials: Stainless steel housing with all fluid-wetted components constructed from AISI 316 stainless steel.
Safety Limits: Overpressure threshold of 1.5×F.S. and a burst/broken pressure rating of 3×F.S.
Response Time: 10 ms.
![]()